Non-directive probe field fixed gas detector (without display)SI-100C
chinacoal07@gmail.com
https://www.chinacoalintl.com#tanya
https://m.chinacoalintl.com/
we provide service of enterprise's customs declaration, inspection.
https://www.chinacoalintl.com#tanya
https://m.chinacoalintl.com/
we provide service of enterprise's customs declaration, inspection.
Co gas detector, fixed
gas detector, H2S gas detector, natural gas detector
Product Introduction
Device description
SI-100C is a fixed gas detector installed
in a place where potential gas hazard exists to measure oxygen, toxic gas and
combustible gas without LCD display. It can be connected to the controller with
a standard 4-20mA analog outputs.
Major Applications
Steelworks, petrochemical, refining,
shipbuilding, wastewater treatment plants and septic tank, LPG tank facilities,
LNG gas plant
Features
01. Explosive proof structure
02. Water/dust proof structure
03. 4-20mA Analog outputs
04. Built-in Calibration Mode
Specification
|
Model
|
SI-100C
|
|||
|
Measuring gas
|
Combustible gas
|
CO
|
H2S
|
O2
|
|
Measuring type
|
Diffusion Type
|
|||
|
Measuring method
|
Electrochemical
|
Electrochemical
|
Electrochemical
|
Electrochemical
|
|
Measuring range
|
0~100%LEL
|
0~500ppm (std)
(Programmable) |
0~100ppm (std)
(Programmable) |
0~30% Vol.
|
|
Sensor life time
|
> 5 years
|
> 2 Years
|
> 2 Years
|
> 18 Month
|
|
Response time
|
< 15sec/90%scale
|
< 30sec/90%scale
|
< 30sec/90%scale
|
< 15sec/90%scale
|
|
Accuracy
|
±3%/Full scale
|
|||
|
Parameter Control
|
Switch(calibration), Admin
Console(maintenance, OPTION)
|
|||
|
Operation mode display
|
2-LED(Operating and Zero Cal, Span Cal.
LED)
|
|||
|
Output signal
|
4-20mA DC(3wire)
|
|
||
|
Cable/Distance
|
Signal cable : 3-wire >
1.5sq(AWG16)/2,500m max |
|
||
|
Conduit connection
|
NPT 3/4" (2way)
|
|||
|
Mounting type
|
Wall mount
|
|||
|
Setting
|
1 Switch Interface(Calibration), Console
set available(Option)
|
|||
|
Remote Set
|
via Console (Zero Calibration, Span
Calibration, Calibration Gas Concentration Set, Factory default, 4-20mA
Calibration, Range Set, Data Logging)
|
|||
|
Operating temperature
|
-20℃~50℃
|
|||
|
Operating humidity
|
5% to 95% RH(Non-condensing)
|
|||
|
Operating power
|
7V to 40V INPUT DC
(12V or 24V DC 60mA normal ) |
|
||
|
Material
|
Aluminium, Stainless steel(STS304)
|
|||
|
Dimensions
|
102(W) × 137(H) × 87(D)mm
|
|||
|
Weight
|
1.0 kg
|
|||
|
Option
|
Console
|
|||
|
Approval
|
Ex d IIC T5 IP65(IECEx)
|
|||

Comments